How many amps does a 7.5 kW motor draw on 460 V? At full load, 12.73 A. The sum uses the power, voltage, power factor and efficiency off the nameplate, and it runs backwards too.
This is the current from the formula, for the power factor and efficiency entered. Size the overload relay and the cable from the nameplate current.
Nameplate power is what the motor delivers at the shaft. It takes more than that from the line, because you divide by efficiency, and from there voltage and power factor give the current. On a three-phase supply the voltage is line to line and the square root of three comes in.
The first is for three-phase, the second for single-phase. I: line current (A) · P: shaft power (kW) · U: line-to-line voltage (V) · cos φ: power factor · η: efficiency, 0.7 to 0.95 depending on size.
Worked example · a 7.5 kW four-pole motor
Using what the calculator starts with: 7.5 kW at the shaft on a 460 V three-phase supply, power factor 0.84 and efficiency 88 %.
Power factor and efficiency change with motor size. The table gives typical values for 4-pole IEC motors and the current that results on 380 V three-phase. At 400 V multiply by 0.95, at 460 V by 0.83 and at 230 V three-phase by 1.65.
Three-phase 4-pole motors, 50 Hz: typical values and approximate full-load current
| Power (kW) | HP | Typical η (%) | Typical power factor | Current at 380 V (A) |
|---|---|---|---|---|
| 0.37 | 0.5 | 72 | 0.72 | 1.1 |
| 0.75 | 1.0 | 78 | 0.76 | 1.9 |
| 1.5 | 2.0 | 82 | 0.80 | 3.5 |
| 2.2 | 3.0 | 84 | 0.81 | 4.9 |
| 4 | 5.4 | 86 | 0.82 | 8.6 |
| 5.5 | 7.4 | 87 | 0.83 | 11.6 |
| 7.5 | 10.1 | 88 | 0.84 | 15.4 |
| 11 | 14.8 | 89 | 0.85 | 22.1 |
| 15 | 20.1 | 90 | 0.85 | 29.8 |
| 22 | 29.5 | 91 | 0.86 | 42.7 |
The current from the formula rests on typical values or on the ones you enter. The nameplate current is the one that sizes the overload relay and the cable. With the amps in hand you can go the other way: switch the selector and get the shaft power. To turn that power into torque, use the torque and power calculator.
About 13 A at full load by the formula: 12.66 A with 88 % efficiency and a 0.84 power factor; the NEC table lists 14 A. At 380 V it is about 15 A.
I = P × 1000 / (√3 × U × cos φ × η), with P the shaft power in kW and U the line-to-line voltage. For a 7.5 kW motor on 460 V that comes to 12.73 A.
Size the overload relay and the cable from the nameplate current. The calculator gives the figure from the formula, for the power factor and efficiency entered.
The full table and the explanation are in chapter 24 of the machinist's handbook: Basic mechanics: power, torque and pressure.
Sources: IEC 60034-1 (rotating electrical machines: rating and performance); IEC 60072-1 (dimensions and output series of IEC frames) and EN 50347 (power-to-frame assignment). Current is worked out with I = P / (√3 · U · cos φ · η); the η and power factor values in the table are typical and the nameplate current is the real one.
Motor torque from power and rpm, or the other way round, plus what comes out of the gearbox.
Open the calculator →Belt length from pulleys and centers, or centers for a given belt, with wrap and speeds.
Open the calculator →Twenty-five chapters of shop tables, drawings and worked examples.
See the contents →We make shafts, pulleys, frames and welded assemblies, delivered ready to fit.
© Indumor 2010–2026 — Industrial steel fabrication, Córdoba, Argentina